Door side heating system GC-14MC-WZ
Door side heating system GC-14MC-WZ
basic information
It is installed on the side or above the gate to bear the intrusion of cold wind into the thermal load of the gate, which is called door side heating equipment.
Table of performance parameters of door side heating equipment
Model |
Rated Air volume (m3/h) |
Rated Heating load (kW) |
In and out water temp. (℃) |
Room temperature (℃) | |||||
12 | 14 | 16 | 18 | 20 | 22 | ||||
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
Heat load (kW) |
||||
GC-14MC-WZ | 1329 | 14 | 70/50 | 10.42 | 9.98 | 9.55 | 9.12 | 8.68 | 8.25 |
60/50 | 9.33 | 8.90 | 8.47 | 8.03 | 7.60 | 7.16 | |||
45/40 | 6.62 | 6.19 | 5.75 | 5.32 | 4.88 | 4.45 |
The door side heating equipment chooses the table
Model |
Rated wind speed (m/s) |
Rated supply Temp. (℃) |
Rated |
Rated Heat Load |
Coefficient of local resistance |
Rated voltage (V)50Hz |
Rated input Power(kW) |
Noise value [dB(A)] |
Weight (kg) |
Scope of apply |
GC-14MC-WZ | 12 | 49 | 1329 | 14 | 1.34 | DC 24V | 0.2 | 55 | 29 | 6-40m wide gate |
Door side heating equipment dimension drawing
Table of Door side heating equipment boundary dimension (mm)
Model | L | L1 | W | W1 | W2 | H | H1 | H2 | D1 | D2 |
Size of air outlet (Size * number) |
GC-14MC-WZ | 1014 | 1092 | 658 | 460 | 75 | 320 | 121 | 30 | DN25 | DN25 | φ140×2 |